Sensible heat calculator

Heat needed to warm, or removed to cool, a mass of material without a change of state: Q = mcΔT, in kJ and kWh, with an optional heat-up time for a heater of known output.

An energy balance for one mass. It ignores losses, vessel heat capacity and stratification, and it is not a heating or cooling load calculation.

Worked examples

EXAMPLE 1: Water batch with a 3 kW heater

50 kg × 4.186 × 20 K = 4,186 kJ, which is 1.163 kWh. A 3 kW element supplies that in 1.163 / 3 × 60 ≈ 23.3 minutes if nothing is lost.

EXAMPLE 2: Hot-water cylinder from cold

120 kg (about 120 litres) from 10 °C to 55 °C is a 45 K rise: 120 × 4.186 × 45 = 22,604 kJ, or 6.279 kWh. At 3 kW that is about 2.09 hours before standing losses, which is why a cylinder reheat feels slow on an immersion heater alone.

Where this fits

Use it for one-off heat-up and cool-down sums: a process tank, a cylinder, a concrete pour warmed in winter, a mass of air in a room. For steady heat lost through walls and roofs, the quantity is a rate, not a lump of energy; use the U-value and fabric heat loss pages instead. For heat carried by a moving airstream, find the mass flow first (volume flow × about 1.2 kg/m³), using the duct velocity page for the airflow.

Reading the result

A positive Q is heat added; a negative ΔT gives a negative Q, which is heat that must be removed. Real heat-up times are longer than the ideal figure because the vessel, pipework and surroundings take heat too. If a material melts, freezes, boils or condenses within the range, add the latent heat on top: it is often far larger than the sensible part.

Typical values

MaterialSpecific heat (kJ/kg·K, approximate)
Water4.19
Ice2.1
Air (constant pressure)1.005
Aluminium0.90
Concreteabout 0.88
Steelabout 0.49

EXAMPLE: warming the air in a 500 m³ room (about 600 kg) by 10 K takes 600 × 1.005 × 10 ≈ 6,030 kJ, or 1.68 kWh, before any fabric or ventilation loss.

Common mistakes

  • Entering litres of a gas as kilograms. Gas mass depends on density; air is about 1.2 kg/m³ at room conditions.
  • Using J/kg·K values (4,186) in a kJ field, which gives answers 1,000 times too large.
  • Leaving out latent heat when water freezes or boils within the range.
  • Treating the ideal heat-up time as the real one.
  • Using Q = mcΔT for a continuous load, which needs a rate (kW), not an energy (kWh).

How to use

Enter the mass, the specific heat capacity and the temperature rise or fall. Add a heater output in kW if you want an ideal heat-up time; leave it blank otherwise.

Edge cases

  • A negative temperature change returns a negative Q (heat removed). No heat-up time is shown for it.
  • Zero mass gives zero heat. Specific heat must be greater than zero.
  • A heater output of zero or less is rejected; leave the field blank instead.
  • Values above 10¹² are rejected.

Questions

How much heat does 100 kg of water need for a 40 K rise?

100 × 4.186 × 40 = 16,744 kJ, or about 4.65 kWh.

Why show kWh as well as kJ?

Heater ratings and energy bills use kW and kWh, so kWh compares directly with a heater size or a meter reading.

Does 1 K equal 1 °C here?

For a temperature change, yes. Only absolute temperatures differ by 273.15.

Sources

Last checked 19 October 2026. Figures recomputed for this revision; specific heats are approximate room-temperature values. See methodology and the disclaimer.