Duct air velocity calculator
Mean velocity from airflow and duct size. Not a duct sizing, pressure drop or noise assessment.
Preliminary only. Use internal dimensions. Velocity limits, pressure loss and noise are design decisions.
Worked examples
EXAMPLE 1: Rectangular branch
Q = 0.5 m³/s in a 400 × 250 mm duct. A = 0.4 × 0.25 = 0.1 m². v = 5 m/s. Dh = 2 × 400 × 250 / 650 = 307.7 mm. pv = 0.6 × 5² = 15 Pa.
EXAMPLE 2: Circular duct
Q = 0.3 m³/s in a 250 mm circular duct. A = π × 0.25² / 4 = 0.0491 m². v = 6.11 m/s, pv ≈ 22.4 Pa.
Reading the result
The velocity is the average over the section; the centre runs faster and the walls slower. Velocity pressure is useful because fitting losses are often expressed as a loss coefficient multiplied by it. Hydraulic diameter lets you use round-duct friction charts for rectangular ducts, with care for very flat aspect ratios.
If the velocity looks high, check noise and pressure drop with a design method. If it looks very low, the duct may be oversized for the space it takes up.
Typical values
EXAMPLE velocities for 0.5 m³/s in different rectangular sizes:
| Duct (mm) | Area (m²) | Velocity (m/s) |
|---|---|---|
| 300 × 200 | 0.06 | 8.33 |
| 400 × 250 | 0.10 | 5.00 |
| 500 × 300 | 0.15 | 3.33 |
| 600 × 400 | 0.24 | 2.08 |
These are worked numbers, not recommended limits.
Common mistakes
- Using external dimensions or nominal sizes instead of internal dimensions.
- Mixing l/s and m³/s: 500 l/s = 0.5 m³/s.
- Using hydraulic diameter to calculate the area. Use the real area for velocity.
- Treating mean velocity as a noise check.
- Forgetting lining thickness in lined ducts.
How to use
Choose the shape, enter the airflow in m³/s, then either the width and height or the diameter in millimetres. Fields for the other shape are ignored.
Edge cases
- Airflow may be zero (velocity zero) but not negative.
- The size fields for the chosen shape must be filled and greater than zero.
- Air density is fixed at 1.2 kg/m³; at other temperatures or altitudes velocity pressure changes.
- Inputs over 10¹² are rejected.
Questions
Where do design velocity limits come from?
From CIBSE Guide B, the project specification and the acoustic design. Confirm the edition in use.
Can I enter l/s?
Divide by 1000 first. 250 l/s is 0.25 m³/s.
Why is the hydraulic diameter not the same as an equivalent diameter?
Equivalent diameter for equal friction is a different formula. Hydraulic diameter is 4A/P.
Basis
This tool uses the formula shown under Method. It is standard arithmetic or physics and relies on no external data set or design standard, so check any values you enter against your own project data.
Last checked 17 October 2026. Preliminary figure only. See methodology and the disclaimer.