Home · Calculators

U-value calculator from layers

Simple layer-by-layer U-value. Not a full BS EN ISO 6946 calculation and not a Building Regulations compliance check.

Preliminary only. Use manufacturers’ declared λ values and a full BS EN ISO 6946 calculation for compliance.

Worked examples

EXAMPLE 1: Cavity wall

Brick 102.5 mm (λ 0.77), PIR 100 mm (λ 0.022), block 100 mm (λ 0.15), plasterboard 12.5 mm (λ 0.21). Layer R = 0.133 + 4.545 + 0.667 + 0.060 = 5.405. Rtotal = 0.13 + 5.405 + 0.04 = 5.575 m²K/W, so U ≈ 0.179 W/m²K before corrections.

EXAMPLE 2: Insulated loft (roof)

Mineral wool 200 mm (λ 0.040) and plasterboard 12.5 mm (λ 0.21), heat flowing upward. Rtotal = 0.10 + 5.0 + 0.060 + 0.04 = 5.200 m²K/W, U ≈ 0.192 W/m²K. Joists bridging the insulation would raise this; the tool does not include them.

Reading the result

A lower U-value means less heat loss. Multiply U by area and temperature difference for the fabric heat loss in watts, as on the heat loss page. The insulation layer usually dominates; the surface resistances matter most for poorly insulated elements.

Where timber studs, joists or metal fixings cross the insulation, the real U-value is higher. Use the full method or software that follows BS EN ISO 6946 and BR 443 for anything beyond a first look.

Typical values

Surface resistances (BS EN ISO 6946:2017):

Heat flowRsi (m²K/W)Rse (m²K/W)
Horizontal (walls)0.130.04
Upward (roofs)0.100.04
Downward (floors)0.170.04

EXAMPLE λ values often quoted (check the product’s declared value): PIR board about 0.022, mineral wool 0.032–0.044, plasterboard about 0.21, softwood about 0.13 W/mK.

Common mistakes

  • Entering thickness in metres when the field asks for millimetres.
  • Using a brochure λ rather than the declared value for the product.
  • Adding an unventilated cavity as if it had no resistance, or a ventilated one as if it did.
  • Ignoring repeating thermal bridges such as studs and joists.
  • Using this for ground floors, which need BS EN ISO 13370.

How to use

Choose the element so the right surface resistances are used. Enter each layer’s thickness in millimetres and conductivity in W/mK. Leave unused layers blank or set the thickness to 0.

Edge cases

  • A layer with a thickness needs a λ greater than zero.
  • At least one layer is needed.
  • Air gaps, bridging and fixings corrections are not applied.
  • Inputs over 10¹² are rejected.

Questions

Does this show compliance with Part L?

No. Compliance needs a full calculation, accredited details and the current Approved Document.

Can I add an air cavity?

Enter it as a layer with an equivalent λ only if you have its thermal resistance; λ = thickness / R.

Why is my U-value lower than the manufacturer’s?

Their figure probably includes bridging and fixings corrections.

Sources

  • BS EN ISO 6946:2017
  • BRE Report BR 443 (2019)

Last checked 17 October 2026. Preliminary figure only. See methodology and the disclaimer.