Worked examples
Example 1: Insulated wall
U 0.28 W/m²K, 40 m², 20 K difference: Q = 224 W.
Example 2: Window area
U 1.4 W/m²K double glazing, 12 m², 21 K (21 °C inside, 0 °C outside): Q = 353 W. Less than a third of the area loses more heat than the wall, which is typical of glazing.
Reading the result
Add the elements to get a fabric total. Enter a volume and air-change rate to add ventilation loss. Thermal bridging and intermittent heating are not included and can be a large share of the total.
ΔT is the difference between inside and outside design temperatures. A 1 K difference in °C is the same as 1 K.
The table values are for orientation. Use the U-values from the specification or an energy assessment for the real building.
Typical values
| Element | Typical U-value (W/m²K) |
|---|---|
| Insulated new cavity wall | 0.18–0.28 |
| Solid brick wall, uninsulated | about 2.0 |
| Double glazing | 1.2–1.6 |
| Single glazing | about 5.0 |
Common mistakes
- Using the room temperature rather than the inside–outside difference.
- Forgetting floors, roofs and doors in the total.
- Leaving out ventilation loss, which is often a third or more of the total.
How to use
Enter the U-value in W/m²K, the element area in m² and the inside-to-outside temperature difference in K. The result is the steady fabric heat loss Q = UAΔT in watts.
Edge cases
- Zero U-value, area or temperature difference gives zero loss. Negative U-value or area is rejected.
- A negative temperature difference gives a negative result, which means heat flows in.
- Thermal bridging, ventilation and infiltration are not included and can be a large share of the total.
Questions
What does a 6 m² window at U 1.4 lose at 22 K?
About 185 W.
And an 80 m² roof at U 0.16 with a 22 K difference?
About 282 W, larger than the window because of the area even though the U-value is much lower.
How do I get the whole-room figure?
Repeat the calculation for each element, walls, windows, roof and floor, using its own U-value and area, and add them. Then add ventilation loss, roughly 0.33 × air changes per hour × room volume × ΔT in watts. The ventilation part is often as large as the fabric loss in older buildings.
Basis
This tool uses the formula shown under Method. It is standard arithmetic or physics and relies on no external data set or design standard, so check any values you enter against your own project data.
Last checked 14 October 2026. See the disclaimer.