Home · Calculators

Voltage drop calculator

A first-pass drop for a copper run, corrected for conductor temperature, or from a tabulated mV/A/m value.

Method, step by step

  1. Resistance of one conductor. R = ρL/A, with ρ = 1.72×10⁻⁸ Ω·m for copper at 20°C and A in m², then increased by 0.393% per kelvin above 20°C. A 2.5 mm² conductor is about 6.9 mΩ per metre at 20°C and about 8.2 mΩ per metre at 70°C.
  2. Go and return. In a single-phase circuit the current flows out on the line conductor and back on the neutral, so the loop length is twice the one-way route length. Type the one-way length; the page doubles it.
  3. Drop and percentage. Drop = I × Rloop. Percentage = drop ÷ supply voltage × 100, using the nominal voltage you type.

Worked example

A 16 A load at the far end of a 25 m radial circuit in 2.5 mm² copper, on a 230 V single-phase supply.

  • Loop length: 2 × 25 = 50 m.
  • Loop resistance at 20°C: 1.72×10⁻⁸ × 50 ÷ 2.5×10⁻⁶ = 0.344 Ω. At 70°C: 0.344 × 1.1965 = 0.412 Ω.
  • Drop at 70°C: 16 × 0.412 = 6.59 V, which is 2.9% of 230 V. At 20°C it would be only 5.50 V, or 2.4%, which is why the tool defaults to 70°C.

Now the same circuit using the tabulated method. The BS 7671 Appendix 4 tables give voltage drop in mV/A/m at the conductor’s maximum operating temperature, with go and return already included. For 2.5 mm² 70°C thermoplastic flat twin-and-earth cable the tabulated value is 18 mV/A/m, so the drop is 18 × 16 × 25 ÷ 1,000 = 7.2 V, about 3.1%.

The tabulated figure is about 9% higher than the 70°C estimate, because the tables use the standard maximum conductor resistance rather than the nominal cross-section. Enter the tabulated mV/A/m value for your cable whenever you have it.

The BS 7671 figures, stated carefully

BS 7671 requires the voltage at the terminals of fixed current-using equipment to be suitable for that equipment. Appendix 4 has long given voltage-drop values that are deemed to satisfy that requirement: for an installation supplied directly from a public low-voltage distribution system, 3% for lighting and 5% for other uses, with higher values (6% and 8%) for a private low-voltage supply. Check the values in the current amendment before relying on them. On a 230 V supply, 3% is 6.9 V and 5% is 11.5 V.

Two points are often missed. First, the percentage is measured from the origin of the installation to the equipment, so the distribution circuit and the final circuit share the allowance. Second, these are deemed-to-satisfy values, not a pass mark for one cable in isolation: a larger drop can be acceptable where the equipment standard allows it, for example during motor starting.

In the worked example, the 70°C estimate gives 2.9% and the tabulated method gives 3.1%. As a lighting circuit, it would already be over 3% before any submain drop is added. Quoting the estimate as compliance would get that wrong. Check the values in the edition and amendment of BS 7671 in force for your project.

Assumptions

  • Copper at the temperature you enter, 70°C by default. Use the rating of the cable, or the tabulated value.
  • Resistive only. Reactance and power factor are ignored. For larger cables the Appendix 4 tables give separate resistive and reactive components, and reactance becomes a bigger share of the drop as the conductor size increases.
  • Single-phase uses a factor of 2. Balanced three-phase line-to-line uses √3 × I × R per conductor.
  • All the current is drawn at the far end. Loads spread along a circuit, such as lighting points, give a smaller drop than this figure.
  • The nominal supply voltage. The UK declared supply is 230 V with a tolerance of +10% / −6%, so the voltage at the origin can be lower than nominal.

Limitations

This is not cable selection. Current-carrying capacity, grouping, ambient temperature, thermal insulation, the protective device, earth fault loop impedance and disconnection time are all separate checks, and any one of them can decide the cable size before voltage drop does. Use this page to see the order of a copper run before an electrical design. The design uses the regulation method and a competent designer.

Sources

Last checked 9 November 2026. Current edition: BS 7671:2018+A4:2026. Worked figures are scenarios. See methodology and the disclaimer.