Home · Guides

Electrical calculations from Ohm's law to kVAr

Start from the load, then the current, then the cable, then the correction. Stop before protection and cable selection. The worked case follows one small workshop supply.

One workshop supply, step by step

Step 1: the three-phase load. A balanced load at 400 V line, 32 A and power factor 0.85 is √3 × 400 × 32 × 0.85 ≈ 18.84 kW. √3 appears once, because 400 V is line-to-line. Use three-phase power.

Step 2: correction. Raising the power factor from 0.85 to 0.95 needs P(tan φ₁ − tan φ₂) ≈ 5.48 kVAr. At the same 18.84 kW, line current falls from 32 A to about 28.6 A. That is a difference of tangents, not a capacitor selection. Use power factor.

Step 3: a single-phase circuit. One radial circuit from the board feeds a 230 V load at 10 A, power factor 0.9: 2.07 kW. Use single-phase power.

Step 4: the cable. The circuit is designed for 16 A over 25 m of 2.5 mm² copper. Resistance of the go-and-return path at 20°C is about 0.0172 × 50 / 2.5 = 0.344 Ω. The voltage drop is about 5.5 V, or 2.4% of 230 V, and about 88 W is lost as heat in the cable. Use voltage drop. This is a resistivity screen at 20°C; BS 7671 tabulated values for conductor temperature and reactance will give a different figure.

Step 5: checking with Ohm’s law. 5.5 V across 0.344 Ω is 16 A, which closes the loop. A 230 V heater of 46 Ω draws 5 A and dissipates 1,150 W. Use Ohm’s law.

Smaller relationships

Resistors of 10 Ω and 15 Ω are 25 Ω in series and 6 Ω in parallel. Use resistors. An unloaded divider of 1 kΩ over 2 kΩ on 12 V gives 8 V, until something draws current from it. Use voltage divider.

The chain at a glance

StepResult
Three-phase load18.84 kW
Correction5.48 kVAr
Corrected current28.6 A
Cable drop5.5 V (2.4%)
Cable loss88 W

Where the chain stops

Protective device selection, earth fault loop impedance, disconnection times, grouping and installation method all come from BS 7671 and the manufacturer’s data. Quoting the Step 4 figure as a BS 7671 voltage drop is the misread this guide is here to stop.

Changing the cable

Repeat Step 4 with 4 mm² instead of 2.5 mm². The go-and-return resistance at 20°C falls to about 0.0172 × 50 / 4 = 0.215 Ω. At 16 A the drop is about 3.4 V, or 1.5% of 230 V, and the heat lost in the cable falls to about 55 W. The larger cable costs more but loses less energy and leaves more of the voltage-drop allowance for the rest of the installation.

ConductorResistance (Ω)Drop at 16 ALoss
2.5 mm²0.3445.5 V (2.4%)88 W
4 mm²0.2153.4 V (1.5%)55 W

Reviewing an electrical chain

  • Is the voltage the right one: 400 V line for three-phase, 230 V for single-phase?
  • Is the power factor the load’s actual value at the operating point?
  • Is the length the route length one way, with the tool doubling it for go and return?
  • Are the screens labelled as screens in the report?

For the checks that a circuit design needs beyond these tools, see electrical limits.

Questions

Why does correction reduce current?

Capacitors supply the reactive current locally, so the supply only carries the real current plus the remaining reactive part. At 0.95 the same 18.84 kW needs about 28.6 A instead of 32 A.

Is 2.4% acceptable?

That depends on the voltage-drop values the current edition of BS 7671 gives, the type of load and the drop in the rest of the installation. The 20°C screen is not the figure to compare.

Balancing single-phase loads

Three 7 kW single-phase loads, one on each phase of a 400 V supply, draw about 30.4 A per phase. A single 21 kW balanced three-phase load draws about 30.3 A per line at unity power factor, effectively the same. Put all three on one phase and that phase carries about 91 A while the others carry none, which is why loads are spread across phases.

Why does the electrical chain stop before protection?

Because protection depends on the device type, the fault current, the earthing arrangement and the installation method, none of which these tools know. A screen that pretended to cover them would give false confidence. The chain is useful for seeing the size of the load, the effect of correction and the order of the voltage drop.

What if the load is not balanced?

Work each phase separately with its own current and the 230 V phase voltage, then add the phase powers. The three-phase formula assumes equal currents and power factors on all three lines; the neutral carries the imbalance.

Related: Electrical limits · Standards · Glossary

Sources

Last checked 14 October 2026. Current edition: BS 7671:2018+A4:2026. The logic is the textbook relationship named above. It is not a code check. See standards these tools do not replace.