Three-phase power calculator
A steady balanced load. Not a cable size, discrimination study or motor-start check.
Worked examples
Example 1: 32 A supply
400 V, 32 A, pf 0.85: P = 18.84 kW, S = 22.17 kVA.
Example 2: 63 A supply
400 V, 63 A, pf 0.9: P = 39.28 kW, S = 43.65 kVA.
Reading the result
The formula assumes a balanced load. Unbalanced loads need each phase checked.
Use the line-to-line voltage (400 V in the UK), not the phase voltage (230 V).
Typical values
| Supply (400 V, pf 0.9) | Real power |
|---|---|
| 16 A | 9.98 kW |
| 32 A | 19.95 kW |
| 63 A | 39.28 kW |
| 100 A | 62.35 kW |
Common mistakes
- Using 230 V instead of 400 V with the √3 formula.
- Using the breaker rating as the running current.
- Leaving out the power factor for motor loads.
- Applying a balanced formula to an unbalanced load.
How to use
Enter the line voltage, the line current and the power factor of a balanced load. The result is real power P = √3 × V × I × pf and apparent power S = √3 × V × I.
Scope: For single-phase circuits, use single-phase power.
Edge cases
- Zero voltage or current gives zero. Negative values are rejected; power factor must be greater than 0 and no more than 1.
- Use the line-to-line voltage (400 V on a UK supply), not the phase voltage of 230 V.
- The formula assumes a balanced load. Unbalanced loads need each phase worked separately.
Questions
What does 63 A at 400 V and pf 0.9 give?
About 39.3 kW and 43.6 kVA.
What current does an 11 kW motor draw at pf 0.85?
I = P / (√3 × V × pf) ≈ 18.7 A, before efficiency is allowed for.
Why does √3 appear?
In a balanced three-phase system the line voltage is √3 times the phase voltage. Real power is three times the phase power, 3 × Vphase × I × pf, which equals √3 × Vline × I × pf. Using 230 V in this formula would understate the power by √3.
Can I use this for a star or delta motor?
Yes, as long as you enter line voltage and line current. Whether the windings are star or delta connected, the line values give the same total power in this formula.
Sources
Last checked 14 October 2026. Electrical design is to BS 7671:2018+A4:2026. A scenario, not a design. See methodology, standards and the disclaimer.