Worked examples
Example 1: Mixed load
230 V, 10 A, pf 0.9: P = 2.07 kW, S = 2.30 kVA.
Example 2: Resistive load
A 13 A heater at 230 V and pf 1.0: P = S = 2.99 kW.
Reading the result
Current and voltage are RMS values. Use the measured or rated current, not the protective device rating.
Power factor below 1 means more current for the same real power.
Most domestic and small commercial circuits are single phase at 230 V. Current, not power, sets the cable and protection, so kVA is often the more useful number.
Typical values
| Load | Typical power factor |
|---|---|
| Resistive heater | 1.0 |
| LED lighting with good driver | 0.9 or better |
| Small induction motor | 0.7–0.85 |
| Lightly loaded motor | below 0.7 |
Common mistakes
- Using the circuit breaker rating as the load current.
- Leaving the power factor at 1.0 for motor loads.
- Confusing kW and kVA when sizing supplies or generators.
How to use
Enter the supply voltage, the current and the power factor. The result is real power P = VI × pf in kilowatts and apparent power S = VI in kVA.
Scope: For balanced three-phase loads, use three-phase power.
Edge cases
- Zero voltage or current gives zero power. Negative voltage or current is rejected.
- Power factor must be greater than 0 and no more than 1. A purely resistive load such as a heater has a power factor close to 1.
- The figure is a steady load. Motor starting currents can be several times higher for a short time.
Questions
What current does a 3 kW kettle draw at 230 V?
About 13 A, which is why it sits on a 13 A plug.
What is the power of 13 A at 230 V and pf 0.8?
About 2.39 kW real power and 2.99 kVA apparent.
Why is kVA larger than kW?
Apparent power is volts times amps; real power is the part that does work. With a power factor of 0.9, a 2.07 kW load needs 2.30 kVA of supply capacity. Cables and protective devices are rated on current, so they see the kVA, not the kW.
What about a three-wire 230 V circuit?
A standard UK single-phase circuit has line, neutral and protective earth. Only line and neutral carry the load current, so the formula P = VI × pf applies with V = 230 V.
Sources
Last checked 14 October 2026. Electrical design is to BS 7671:2018+A4:2026. See the disclaimer.