Electrical figures, short of BS 7671

Three tools sit on the electrical side. Ohm’s law is a resistive relationship. The voltage-drop page is copper resistivity at about 20°C, go and return. Three-phase power is √3 × line voltage × line current × power factor.

Worked three-phase case

400 V, 32 A, power factor 0.85 is 18.85 kW and 22.17 kVA. That is the steady electrical load. It is not the cable size. Diversity, grouping, installation method, disconnection time and voltage drop from the appendix tables are a different calculation, in BS 7671, with the installation method known.

Use three-phase power and the voltage-drop estimate only as far as the label on the page.

How to use the figure in a review

Quote the inputs with the result. A pad pressure without the load and the area cannot be reviewed. A peak flow without the coefficient, the intensity and the area cannot be reviewed. A gear ratio without the tooth counts cannot be reviewed. The page is the screen. The project document is the limit.

Do not paste the result into a published container as design information. Published means the project state, not this site. A preliminary number stays preliminary until the appointed party issues it under the appointment.