What simple electrical calculations leave out of BS 7671

Three tools sit on the electrical side. Ohm’s law is a resistive relationship. The voltage-drop page is copper resistivity at about 20°C, go and return. Three-phase power is √3 × line voltage × line current × power factor.

What each tool actually does

Ohm’s law on this site is V = IR for one resistance. You enter two of voltage, current and resistance, and the page returns the third. It is a steady relationship. It does not know the cable route, the temperature or whether the load is a motor.

The voltage-drop page estimates drop from current and the resistance of the go and return conductors, using a copper resistivity near 20°C. Length is the route length you type. The result is a volt drop for that length. It is not a percentage limit taken from an appendix table, and it does not show that the circuit will disconnect in time.

In that formula, voltage and current must be the line values. Power factor is the cosine of the phase angle on a balanced load. Kilowatts are real power. Kilovolt-amperes are the apparent power the supply has to provide.

Where the figure stops

Cable size also depends on installation method, grouping, ambient temperature and the protective device. Earth-fault loop impedance and disconnection time are BS 7671 checks, and they are not on these pages. Diversity is a project decision. It is not a factor hidden in the arithmetic.

Use the result to see the order of the steady load, then open the wiring regulations and the cable data for the actual route. A kilowatt figure in a published container is not a circuit design.

Worked three-phase case

400 V, 32 A, power factor 0.85 is 18.84 kW and 22.17 kVA. That is the steady electrical load. It is not the cable size. Diversity, grouping, installation method, disconnection time and voltage drop from the appendix tables are a different calculation, in BS 7671, with the installation method known.

Use three-phase power and the voltage-drop estimate only as far as the label on the page.

Scope: this guide lists the checks that sit beyond the site’s electrical tools. For the worked calculation chain, see electrical logic.

The checks a circuit design needs

CheckWhat it depends onOn this site?
Design currentLoad, diversity, power factorPartly: steady load only
Protective device ratingDesign current and cable capacityNo
Current-carrying capacityInstallation method, grouping, ambient temperature, thermal insulationNo
Voltage dropTabulated mV/A/m at operating temperature, route lengthScreen at 20°C only
Earth fault loop impedanceExternal impedance and circuit conductor resistanceNo
Disconnection timeDevice type and fault currentNo

Why conductor temperature matters

Copper resistance rises by about 0.4% per kelvin. The go-and-return resistance of a 25 m circuit with a 2.5 mm² line conductor and a 1.5 mm² protective conductor, worked from resistivity, is about 0.46 Ω at 20°C and about 0.55 Ω at 70°C. Loop impedance checks use the higher, operating-temperature value, so a figure taken at room temperature is about a sixth too low. The external impedance, supplied by the network operator or measured, is added to give the total loop impedance, which is then compared with the maximum for the protective device in BS 7671.

Diversity is a decision

Adding every connected load gives the worst case, which rarely happens. Diversity reduces the design current to what is likely to run at once. It is a judgement made by the designer using guidance and knowledge of how the building is used. It is not a factor these tools apply, and a calculator figure should not hide one.

Questions

If the voltage-drop screen passes, is the cable fine?

Not necessarily. The cable must also carry the current in its installation conditions and allow the device to disconnect a fault in time. Any one of those can govern.

What should a review note say?

State the load, the power factor, the length, the conductor size and which figures are screens. For example: “18.84 kW steady load at 400 V, pf 0.85, 32 A; voltage drop screened at 20°C; cable selection to BS 7671 by the designer.”

Why is the external impedance needed?

The fault current flows through the supply as well as the circuit. Without the external part, the loop impedance and the disconnection check cannot be completed.

Is a voltage-drop figure needed for every circuit?

Every circuit design needs to show that voltage drop is acceptable, but small, short final circuits are often well inside the values with little calculation. Long runs, high currents and submains are where it matters, so check those first.

Does a larger cable always help?

It lowers drop and loop impedance, but it may not fit the device terminals or the containment, and it costs more. Choose the size the design checks need.