U-values and fabric heat loss

How a U-value is put together, why simple sums read optimistic, and how to turn the result into watts. The numbers are EXAMPLE figures.

Preliminary only. Building Regulations compliance needs a full calculation to the current standards, declared product data and the current Approved Document.

What a U-value is

A U-value is the rate of heat flow through one square metre of an element for each kelvin of temperature difference across it, in W/m²K. It is the reciprocal of the total thermal resistance. Lower is better: a modern insulated wall is well under 0.3 W/m²K, while an uninsulated solid brick wall can be over 2.

Resistances in series

For a layer of uniform material, the thermal resistance is its thickness in metres divided by its thermal conductivity λ in W/mK. Layers in series add. To the layers you add an internal surface resistance Rsi and an external surface resistance Rse, which represent the still air film and radiation at each face.

BS EN ISO 6946:2017 (current; confirmed by BSI and ISO in 2022) gives the conventional values for plane surfaces: Rsi = 0.13 m²K/W for horizontal heat flow (walls), 0.10 for upward flow (roofs) and 0.17 for downward flow (floors over a space), with Rse = 0.04. BRE report BR 443 (2019 edition) sets out the UK conventions for applying the standard. The U-value calculator uses those surface resistances with up to four homogeneous layers.

EXAMPLE: a cavity wall

Brick outer leaf 102.5 mm at λ 0.77, PIR board 100 mm at λ 0.022, block inner leaf 100 mm at λ 0.15 and plasterboard 12.5 mm at λ 0.21. The layer resistances are 0.133, 4.545, 0.667 and 0.060 m²K/W, so the layers total 5.405. Adding 0.13 and 0.04 gives 5.575 m²K/W and U ≈ 0.179 W/m²K.

Notice where the resistance is: the insulation provides more than 80% of it. Doubling the brick would barely move the result; a few millimetres of insulation would. That is why the declared λ of the insulation matters more than any other input.

Why the simple sum reads optimistic

The layer-by-layer sum assumes every layer is continuous and uniform. Real constructions are not:

  • Timber studs, joists and rafters bridge the insulation. The full method works out an upper and lower limit of resistance and averages them, giving a higher U-value than the simple sum.
  • Wall ties and mechanical fixings that pass through the insulation add a correction.
  • Gaps and poor fit of boards add an air-gap correction.
  • Unventilated, slightly ventilated and well-ventilated air layers are treated differently; a well-ventilated cavity or roof space changes which layers count.

A manufacturer’s published U-value for a build-up usually includes those corrections, which is why it often reads a little higher than a hand sum. If your simple sum is better than theirs, believe theirs.

EXAMPLE: an insulated loft

200 mm of mineral wool at λ 0.040 over 12.5 mm plasterboard, heat flowing upward: Rtotal = 0.10 + 5.000 + 0.060 + 0.04 ≈ 5.20 m²K/W and U ≈ 0.192 W/m²K. Where the wool sits between ceiling joists, the joists form a bridged layer and the real U-value is higher. The calculator does not include them.

Ground floors are different

Heat flowing into the ground depends on the floor’s size and shape, the perimeter and the soil, not just the layers. BS EN ISO 13370 covers ground floors. Do not use a layer sum for a ground-bearing slab.

From U-value to heat loss

Fabric heat loss through an element is U × area × temperature difference. The fabric heat loss calculator does that sum.

EXAMPLE: 40 m² of the cavity wall above at a 20 K difference loses about 0.179 × 40 × 20 ≈ 144 W. The same area at U 0.28 loses 224 W. A solid 215 mm brick wall at λ 0.77, with the same surface resistances, has U ≈ 2.23 W/m²K and would lose about 1,780 W. These are steady-state figures for one element.

A room or building heat loss also needs every other element, thermal bridging at junctions, which is usually handled with a y-value or individual ψ-values, and ventilation and infiltration losses, which can be as large as the fabric loss in a well-insulated building. The sensible heat calculator gives the heat carried by an airflow.

Getting λ values right

Use the manufacturer’s declared thermal conductivity for the specific product, not a generic value. Brick and block conductivities vary widely with density and moisture. EXAMPLE values often quoted are about 0.022 W/mK for PIR board, 0.032–0.044 for mineral wool, about 0.21 for plasterboard and about 0.13 for softwood, but they are only for orientation.

A short checklist

  • Choose the right heat flow direction for the surface resistances.
  • Enter thicknesses in millimetres and λ in W/mK.
  • Use declared λ values and say where they came from.
  • Expect the full method with bridging to give a higher U-value.
  • Use BS EN ISO 13370 for ground floors.
  • Add junctions and ventilation before quoting a heat loss for a room.

Where this stops

A hand U-value is useful to compare options and to check that a supplier’s figure is in the right range. It is not evidence of compliance, and it is not an energy model. Building Regulations calculations, SAP or SBEM assessments and condensation risk analysis need the full methods and the current editions of the documents they cite.

Related tools: U-value from layers · Fabric heat loss · Sensible heat · Weights and heat

Sources

  • BS EN ISO 6946:2017
  • BRE Report BR 443 (2019)