Home · Calculators

Stair rise and going

Pitch and 2R + G for one step, a screen against the Approved Document K (England) Table 1.1 ranges for the stair category you choose, and, from the floor-to-floor height, the number of equal risers in the flight. Geometry only, not Building Regulations approval.

A geometry screen. Headroom, width, landings, handrails, guarding, tapered treads and the rules outside England are not checked.

Worked examples

EXAMPLE 1: Domestic flight, 2,700 mm floor to floor

Target rise 180 mm: 2,700 / 180 = 15 risers exactly, so each rise is 180 mm with 14 goings of 250 mm, 3,500 mm on plan. Pitch = arctan(180/250) = 35.8°, 2R + G = 610 mm. All inside the private-stair figures.

EXAMPLE 2: 2,650 mm with a 240 mm going

2,650 / 180 = 14.72, rounded up to 15 risers of 176.7 mm. With 14 goings of 240 mm the flight is 3,360 mm long on plan. Pitch = arctan(176.7/240) = 36.4°, 2R + G = 593 mm. Rounding down to 14 risers would give 189.3 mm, above the 180 mm target.

Reading the result

Each line of the result is a separate check. Passing 2R + G does not mean a step passes: 220 mm by 220 mm gives 660 mm, inside the band, but a 45° pitch, over the private-stair maximum. Equal risers through the flight matter more to safety than hitting a particular 2R + G; an odd step at the top or bottom is a common cause of falls.

Typical values

Rise × going (mm)Pitch2R + G
150 × 30026.6°600 mm
170 × 26033.2°600 mm
180 × 25035.8°610 mm
200 × 22541.6°625 mm
220 × 22045.0°660 mm

Common mistakes

  • Rounding the riser count down, which pushes every rise above the target.
  • Counting as many goings as risers; the top step is the landing.
  • Measuring going from the riser face rather than nosing to nosing.
  • Using the private-stair figures for a common stair in a block of flats or a workplace.
  • Checking only one of rise, going, pitch and 2R + G.

How to use

Choose the category, enter the floor-to-floor height if you are planning a whole flight, then a target rise and the going in millimetres. Leave the height blank to check a single step exactly as entered.

Edge cases

  • Rise and going must be greater than zero; a blank floor-to-floor height is ignored.
  • A height smaller than the target rise gives one riser and no goings.
  • The pitch limit is applied only to private stairs, as in Table 1.1.
  • Values above 10¹² are rejected.

Questions

Is 200 mm rise and 225 mm going acceptable for a private stair?

Pitch 41.6° and 2R + G 625 mm, both inside the private-stair figures, but close to the 42° maximum. Building control decides.

Why does my loft stair fail?

Loft conversions often push the rise up and the going down. Check the pitch first; at 220 mm rise, any going under about 244 mm exceeds 42°.

Sources

Last checked 19 October 2026. Limits from Approved Document K, 2013 edition (England), Table 1.1. Not a Building Regulations approval; see the disclaimer.