Pad foundation bearing pressure calculator

Concentric vertical load divided by plan area. Eccentricity and groundwater are ignored.

Worked examples

Example 1: Square pad

400 kN on 1.5 m × 1.5 m is 178 kN/m².

Example 2: Rectangular pad

650 kN on 2.0 m × 2.5 m is 130 kN/m². A larger pad spreads more load at lower pressure.

Reading the result

Compare the average pressure with an allowable or design bearing figure only if you know where that figure came from and whether it is factored. This page does not check bearing resistance, settlement or sliding.

Include the self-weight of the pad and any backfill above it in N if it is significant.

An eccentric load or moment gives a non-uniform pressure that can be much higher at one edge.

Common mistakes

  • Leaving out pad self-weight and backfill.
  • Comparing an unfactored pressure with a factored resistance.
  • Ignoring eccentricity from column moments.

How to use

Enter the vertical load in kN and the plan breadth and length of the pad in metres. The result is the average bearing pressure, load divided by plan area, in kN/m².

Edge cases

  • Zero or negative dimensions are rejected; a zero load gives zero pressure.
  • Include the pad’s own weight and any soil over it in the load if they bear on the same formation.
  • Eccentric load or moment changes the pressure distribution; the average is then not the maximum.

Questions

What does 600 kN on a 2 m × 1.5 m pad give?

200 kN/m². Adding the self-weight of a 0.5 m deep concrete pad (about 37.5 kN) gives about 212.5 kN/m².

Is this the allowable bearing pressure?

No. That comes from the ground investigation and a geotechnical design.

What about a moment at the base?

A moment makes the pressure higher on one side. For a rectangular pad with the resultant inside the middle third, the maximum pressure is P/A × (1 + 6e/B), where e is the eccentricity. A 200 kN/m² average with e = B/12 gives a maximum of 300 kN/m². This page reports only the average.

Should I use factored or unfactored loads?

Use the load combination the geotechnical check asks for. Serviceability and settlement checks normally use characteristic loads; ultimate limit state checks use factored loads against a factored resistance. Write down which one you used beside the result.

Sources

Last checked 14 October 2026. Geotechnical design in the UK is to BS EN 1997-1:2004+A1:2013 until 30 March 2028; BS EN 1997-1:2024 is the second-generation edition. A scenario, not a design. See methodology, standards and the disclaimer.