Concrete maturity calculator

Degree-hours and equivalent age from your temperature log.

Worked example

With the default log and a −10 °C datum, the first interval averages 21 °C for 6 hours, adding (21 + 10) × 6 = 186 °C·h. The calculator adds every interval the same way.

Maturity is not strength

Maturity only measures the heat history. To estimate strength you need a calibration for the same mix, made by testing cubes or cylinders at known maturities. Enter the maturity that calibration gives for your striking strength as the target.

The right datum comes from the calibration. A datum of 0 °C or −10 °C is common. Mixes with cement replacements such as GGBS or fly ash can respond differently to temperature, so a calibration from another mix should not be reused.

Logging the temperature

  • Place the sensor where the concrete stays coolest if the check is for early striking.
  • Record often enough to catch the temperature peak.
  • Keep the original log with the pour record.

The Sadgrove function, sometimes used in the UK, is not included because we could not confirm its published form from a source we opened.

Do not use this result to strike formwork without a calibrated strength relationship and the agreement of the temporary works designer.

The full calculation

Using the default log with a −10 °C datum and a 20 °C reference temperature:

HoursAverage °CLess datumDuration (h)°C·h addedRunning total
0 to 621316186186
6 to 1227376222408
12 to 24283812456864
24 to 482333247921,656
48 to 721828246722,328

Equivalent age is 2,328 ÷ (20 + 10) = 77.6 hours, or 3.23 days at 20 °C. This concrete is slightly ahead of its 72-hour actual age because it ran warmer than the reference on average.

If the calibration gives 1,000 °C·h for your striking strength, the running total passes 864 at 24 hours. The remaining 136 °C·h at 33 °C·h per hour takes about 4.1 hours more, so the target falls at about 28.1 hours.

Why the datum changes the answer

DatumMaturityEquivalent age at 20 °C
−10 °C2,328 °C·h77.6 h
0 °C1,608 °C·h80.4 h

The maturity figures are not comparable with each other. A target from a calibration only applies when the tool uses the same datum as that calibration, so record the datum with the result.

Common mistakes

  • Applying a target from a different mix or a different datum.
  • Entering clock times in place of hours elapsed since the pour.
  • Leaving long gaps in the log, which can miss the temperature peak or a cold night.
  • Starting the count later than the pour, which understates maturity.