Home · Calculators

Power-factor correction

Steady balanced load.

Worked examples

Example 1: Small load

18.85 kW from pf 0.85 to 0.95 needs about 5.49 kVAr.

Example 2: Poorer starting point

45 kW from pf 0.78 to 0.95 needs about 21.3 kVAr. The lower the starting power factor, the more correction each kilowatt needs.

Reading the result

Real power does not change; the apparent power and current fall. For the 45 kW load, kVA drops from 57.7 to 47.4.

Harmonics, resonance, switching steps and over-correction at light load are not considered. Correction equipment is usually stepped.

The multipliers in the table are tan φ₁ − tan φ₂. Multiply by the real power to get a first estimate of the capacitor rating.

Typical values

Starting pf → targetkVAr per kW
0.70 → 0.950.69
0.80 → 0.950.42
0.85 → 0.950.29
0.90 → 0.950.16

Common mistakes

  • Entering kVA instead of kW as the real power.
  • Correcting to unity, which risks leading power factor at light load.
  • Ignoring harmonics from variable-speed drives.

How to use

Enter the real power in kW, the present power factor and the target power factor. The result is the capacitive reactive power needed, Qc = P(tan φ₁ − tan φ₂), in kVAr.

Edge cases

  • Both power factors must be greater than 0 and no more than 1.
  • If the target is lower than the present power factor, the result is negative: no correction is needed.
  • A target of exactly 1 is possible arithmetically, but over-correction on light load can make the power factor leading. Most designs aim for about 0.95.

Questions

How much correction does 50 kW need from 0.8 to 0.95?

About 21.1 kVAr.

Does correction reduce real power?

No. It reduces the current and the kVA the supply carries for the same kW.

What causes a low power factor?

Inductive loads such as induction motors, transformers and older discharge lighting draw reactive current that does no useful work. A lightly loaded motor has a poorer power factor than one at full load, so correction sized for full load can overcorrect when the plant is idle. Electronic loads can also cause harmonic distortion, which capacitor correction does not fix.

Where should capacitors go?

At a large motor they correct only that load and cut the current in its cable. At the main switchboard, an automatic bank corrects the whole site but does not reduce current in the final circuits. The choice depends on the loads and the tariff.

Sources

Last checked 14 October 2026. See the common-calculations note and the disclaimer.